jeol-t330a/succbone
Rahix 1e21222705 succd: Optimize color usage for HP HMI
In the process automation world, there is a trend to move away from
colorful user-interfaces, towards more "boring" colorschemes.  The
argument is about situational awareness - by only using colors to
highlight abnormal situations, they become instantly recognizable to the
operators.

This design philosophy is outlined by the ISA-101 [1] under the name
"High Performance HMI".  While it covers much more than just colors, I
think this is the most important part and the one that is most
applicable for our usecase.

So let's do a bit of HP HMI - reduce colors usage such that only
important information is highlighted.

[1]: https://www.isa.org/standards-and-publications/isa-standards/isa-standards-committees/isa101
2024-10-05 17:37:10 +00:00
..
succd succd: Optimize color usage for HP HMI 2024-10-05 17:37:10 +00:00
panel.pdf succbone: panel: Wire fake-pirani signals to NC contacts 2024-09-27 23:25:11 +02:00
panel.qet succbone: panel: Wire fake-pirani signals to NC contacts 2024-09-27 23:25:11 +02:00
README.md Add a README 2024-09-26 19:14:22 +02:00
relayboard-din-mount.FCStd succbone: Add relay board mount 2024-09-27 01:19:56 +02:00
succbone-control-panel.jpg succbone: Update title pic 2024-09-28 23:35:09 +02:00
succbone-din-mount.FCStd succbone: Add DIN-rail mount CAD model 2024-09-23 05:03:48 +02:00

succbone

succbone is our "automation" system for the vacuum system of the SEM.

succbone control panel

Features

  • Read a TPR280 pirani gauge (0-10V analog input)
  • 8x relay outputs for
    • Roughing pump interlock
    • Diffusion pump interlock
    • Emulate Pump-Down push button
    • Emulate Vent push button
    • Signal two different vacuum levels to the original evacuation controller
      • Rough vacuum reached
      • High vacuum reached