Temperature Measurement & MODBUS Integration #17
|
@ -2,6 +2,7 @@ package main
|
|||
|
||||
import (
|
||||
"context"
|
||||
"net"
|
||||
"time"
|
||||
|
||||
"github.com/simonvetter/modbus"
|
||||
|
@ -35,10 +36,17 @@ func (d *daemon) modbusConnect() error {
|
|||
return nil
|
||||
}
|
||||
|
||||
func (d *daemon) modbusRestart() error {
|
||||
d.modbusClient.Close()
|
||||
return d.modbusClient.Open()
|
||||
}
|
||||
|
||||
// There are currently two devices connected to the modbus.
|
||||
// The first one (slave 1) is a temperature/humidity sensor.
|
||||
// The second one (slave 2) is a PTA8D08 transmitter
|
||||
func (d *daemon) modbusUpdate() {
|
||||
//
|
||||
// Returns whether modbus should restart (only in case of an underlying network error)
|
||||
func (d *daemon) modbusUpdate() bool {
|
||||
var err error
|
||||
|
||||
// Switch to slave 1 (BTA1)
|
||||
|
@ -48,6 +56,9 @@ func (d *daemon) modbusUpdate() {
|
|||
var registersBTA1 []uint16 // temperature, humidity
|
||||
registersBTA1, err = d.modbusClient.ReadRegisters(1, 2, modbus.INPUT_REGISTER)
|
||||
if err != nil {
|
||||
if _, ok := err.(net.Error); ok {
|
||||
return true
|
||||
}
|
||||
klog.Warningf("error while reading registers from BTA1 %v", err)
|
||||
} else if len(registersBTA1) != 2 {
|
||||
klog.Warningf("expected two registers from modbus slave 1, but got %d", len(registersBTA1))
|
||||
|
@ -68,6 +79,9 @@ func (d *daemon) modbusUpdate() {
|
|||
var registersKEC2 []uint16 // temperatures dp
|
||||
registersKEC2, err = d.modbusClient.ReadRegisters(0, 3, modbus.HOLDING_REGISTER)
|
||||
if err != nil {
|
||||
if _, ok := err.(net.Error); ok {
|
||||
return true
|
||||
}
|
||||
klog.Warningf("error while reading registers from KEC2 %v", err)
|
||||
} else if len(registersKEC2) != 3 {
|
||||
klog.Warningf("expected three registers from modbus slave 2, but got %d", len(registersKEC2))
|
||||
|
@ -88,6 +102,9 @@ func (d *daemon) modbusUpdate() {
|
|||
|
||||
digitalInputRegisters, err = d.modbusClient.ReadRegisters(0x81, 8, modbus.HOLDING_REGISTER)
|
||||
if err != nil {
|
||||
if _, ok := err.(net.Error); ok {
|
||||
return true
|
||||
}
|
||||
klog.Warningf("error while reading digital inputs from KEC1 %v", err)
|
||||
} else {
|
||||
// Convert MODBUS words into bools
|
||||
|
@ -140,8 +157,13 @@ func (d *daemon) modbusUpdate() {
|
|||
|
||||
err = d.modbusClient.WriteRegisters(0x01, registerValuesKEC1[:])
|
||||
if err != nil {
|
||||
if _, ok := err.(net.Error); ok {
|
||||
return true
|
||||
}
|
||||
klog.Warningf("error while updating registers %v", err)
|
||||
}
|
||||
|
||||
return false
|
||||
}
|
||||
|
||||
// Call modbusUpdate every 100 milliseconds
|
||||
|
@ -151,7 +173,16 @@ func (d *daemon) modbusProcess(ctx context.Context) {
|
|||
case <-ctx.Done():
|
||||
return
|
||||
default:
|
||||
d.modbusUpdate()
|
||||
shouldRestart := d.modbusUpdate()
|
||||
// the modbus library does not reopen the tcp socket in case of
|
||||
// a connection loss.
|
||||
if shouldRestart {
|
||||
klog.Infof("restarting modbus connection...")
|
||||
err := d.modbusRestart()
|
||||
if err != nil {
|
||||
klog.Warningf("failed to restart modbus %v", err)
|
||||
}
|
||||
}
|
||||
time.Sleep(time.Millisecond * 100)
|
||||
}
|
||||
}
|
||||
|
|